PMS
Fire-protection coatings

PMS Exterior intumescent coating for structural steel

An exterior intumescent steel-protection system for industrial, marine and humid environments, designed together with a compatible primer and sealing topcoat.

PMS室内泳池应用PMS室内泳池应用

PMS室内泳池应用

Material & applications

Product designation

GT-WRP-Fp2.5-Chnitherm PMS · Exterior intumescent fire-protection coating for steel

Exterior intumescent steel system

PMS protects steelwork in industrial, marine and humid environments with a compatible primer and sealing topcoat. Applications include energy facilities, waterside buildings, aquariums, pools and humid indoor steelwork. Specify member section, film thickness, cellulosic fire requirements and environmental exposure together.

Waterside building applications

Waterside building applicationsWaterside building applications

Waterside building applications

Technical data

Technical data & storage

PropertyRequirement / data
Mixed densityApprox. 1.23 g/cm³
Mixed weight solidsApprox. 70±2%
VOC330 g/L; EN ISO11890-1
Flash point26°C
Theoretical consumption500 μm dry / 750–800 μm wet film: 1000 g/m² (0.78 L/m²)
Thickness & usageDry/wet ratio depends on application; use mass and volume figures in their respective conditions
Packaging25 kg
Base colourWhite
Finish colourPMS/TC: RAL; TC726: RAL or NCS subject to the selected finish
Storage conditionsDry, ventilated indoor storage at 5–30°C; never below 5°C; above 25°C reduces shelf life
Shelf life12 months in sealed original containers under normal conditions

Application & system

Surface and coating system

Use qualified contractors and trained applicators. Blast-clean steel to ISO Sa2.5 or power-tool prepare to at least ISO St2. Check existing primer thickness and compatibility; repair corrosion and mechanical damage. Apply compatible primer, PMS and Chnitherm PMS/TC sealing finish. Confirm TC726 separately when specifying that finish.

Application and equipment

Brush, roller or airless application is possible. Complex members may need additional passes to reach the required dry-film thickness. First wet coat over primer: 400 μm; subsequent wet coats may exceed 500 μm, subject to sag control. Airless pump ratio ≥45:1, solvent-resistant hose ≥3/8 inch, nozzle 0.46–0.66 mm / 0.019–0.027 inch. Cleaning agent: Chnitherm thinner100; thinning is normally unnecessary.

Substrate & application requirements

PropertyRequirement / data
PersonnelQualified contractor and professionally trained applicators
Blast cleaningISO Sa2.5
Power-tool preparationAt least ISO St2
Previous coatingDry and free from contamination
Relative humidityMaximum 85%; prevent condensation; temperature at least 3°C above dew point
Surface reviewMeasure old primer thickness, test compatibility and repair mechanical/corrosion damage
RecoatCompletely dry; minimum 16 h, also observe the temperature-specific table
Thinning & cleaningNormally no thinning; clean with Chnitherm thinner100
Brush/rollerAdditional coats may be required for complex surfaces and specified dry-film thickness
Airless equipmentPump ratio ≥45:1; remove screens and filters
Material hose≥3/8 inch, solvent-resistant
Nozzle0.46–0.66 mm / 0.019–0.027 inch
PassesMultiple passes; first wet coat over primer 400 μm; later wet coats may exceed 500 μm
Exterior workAvoid rain during application/drying; brief light rain only after full drying; seal promptly for exterior use and reinforce marine protection

Drying & curing

Temperature-dependent intervals

Allow complete drying before recoating. A general minimum of 16 hours does not override the temperature-specific recommendations: at 15°C the recommended recoat interval is 48 hours. Surface dry, through dry and recoat time are separate criteria.

Drying and recoat by temperature

TemperatureSurface dryThrough dryRecommended recoat
+15°C24 h72 h48 h
+25°C12 h24 h24 h
+40°C8 h24 h24 h

Conditions & precautions

Exterior conditions and safety

Protect from rain during application and drying. An unsealed, fully dry layer tolerates only brief light rain; complete the finish promptly for exterior use and specify additional protection for marine exposure. RH ≤85%; surface ≥3°C above dew point. Confirm the applicable upper substrate-temperature limit. VOC is 330 g/L and flash point 26°C. Follow the current SDS for ventilation, ignition control, transport and disposal.

Documents & specification support

Specify for your project.

Share the application, substrate, area and performance requirements to discuss a coordinated system.

Contact the factory