PMA
Fire-protection coatings

PMA Interior intumescent coating for structural steel

A waterborne intumescent coating for interior steel columns, beams, frames and trusses, specified with compatible primer and protective finishing coats. For intumescent paint for steel projects, discuss the substrate, compatible materials and application conditions with our factory.

PMA钢结构中庭

PMA钢结构中庭

Material & applications

Product designation

GT-NSP-Fp2.0-Chnitherm PMA · Interior intumescent fire-protection coating for steel

Interior steel protection

PMA forms an insulating intumescent char on steel columns, beams, frames and trusses. It is specified with corrosion primer and protective finish. Applications include interior C4 exposure and open or closed sections with HP/A ≤340 m⁻¹. High-humidity kitchens and indoor pools are excluded.

Steel-roof applications

Steel-roof applications

Steel-roof applications

Technical data

Technical data & system consumption

PropertyDataConditions
Density1.3 g/cm³
Weight solids70±2%ISO3233-1998
VOCApprox. 15 g/LEN ISO11890-1
Shelf life12 months, sealed in cool, dry conditions
Theoretical consumption1.9 kg/m² (1.4 L/m²)1 mm dry film; dry/wet ratio depends on application
Brush/roller per coatMaximum 1 kg/m² on vertical surfaces
AK/AE primer0.1 kg/m²40–50 μm dry film
EP61 on galvanised steel0.15 kg/m²50 μm dry film
TOP C / TOP D finish0.13 kg/m²60 μm dry film
CuringApprox. 24 h per coat20°C, 65% RH
Drying before finishAt least 48 h and completely dryBefore TOP finish
Packaging6, 25 or 35 kg plastic pailsWhite
Storage5–30°C, sealed and frost-free12 months
Finish colourRAL, NCS or agreed sampleFor the compatible topcoat

Application & system

Steel and primer preparation

Remove rust, dust, grease, adhesive, lime residue, moisture and incompatible coatings. Blast-clean to EN ISO12944-4 Sa2.5 or manually prepare to St3. Apply AK or AE primer. Clean and degrease galvanised steel before EP61. Check existing primers and repair transport or corrosion damage with AK.

Application and finish

Stir slowly to a uniform consistency; apply by brush, roller or airless spray. Consumption depends on section factor U/A and dry-film thickness. Maximum brush/roller application on vertical surfaces is 1 kg/m² per coat. Use compatible TOP C / TOP D finishes for moisture protection and cleaning. Topcoat colours may follow RAL, NCS or an agreed sample.

Drying & curing

Curing and topcoating

Each coat cures in approximately 24 hours at 20°C and 65% RH. Allow at least 48 hours and complete drying before TOP finishes. Matrix figures are hours. Low temperature, high humidity and thicker films extend drying.

Drying-time matrix

Drying times in hours; wet-film thickness in mm.
RHWet film10°C still10°C airflow20°C still20°C airflow30°C still30°C airflow
30%0.362.54241.5
30%0.683.56352.5
30%1.2124.58463
50%0.31036351.5
50%0.61248463
50%1.2186125103.5
70%0.312610583
70%0.6189127106
70%1.22412189127

Conditions & precautions

Weather and storage

Use trained personnel. Material, surface and ambient temperature must be ≥10°C, RH ≤80% and temperature ≥3°C above dew point. PMA is water-sensitive. Protect during application, drying and transport. For unavoidable outdoor work, avoid rain and confirm a suitable sealing system; Chnitherm 800 is a separate exterior-work option. Temporary rain resistance is not permanent exterior suitability. Store sealed at 5–30°C without frost for 12 months. Follow the SDS and prevent discharge to water or soil.

Documents & specification support

Specify for your project.

Share the application, substrate, area and performance requirements to discuss a coordinated system.

Contact the factory