PMA Interior intumescent coating for structural steel
A waterborne intumescent coating for interior steel columns, beams, frames and trusses, specified with compatible primer and protective finishing coats. For intumescent paint for steel projects, discuss the substrate, compatible materials and application conditions with our factory.
Material & applications
Product designation
GT-NSP-Fp2.0-Chnitherm PMA · Interior intumescent fire-protection coating for steel
Interior steel protection
PMA forms an insulating intumescent char on steel columns, beams, frames and trusses. It is specified with corrosion primer and protective finish. Applications include interior C4 exposure and open or closed sections with HP/A ≤340 m⁻¹. High-humidity kitchens and indoor pools are excluded.
Steel-roof applications
Technical data
Technical data & system consumption
| Property | Data | Conditions |
|---|---|---|
| Density | 1.3 g/cm³ | |
| Weight solids | 70±2% | ISO3233-1998 |
| VOC | Approx. 15 g/L | EN ISO11890-1 |
| Shelf life | 12 months, sealed in cool, dry conditions | |
| Theoretical consumption | 1.9 kg/m² (1.4 L/m²) | 1 mm dry film; dry/wet ratio depends on application |
| Brush/roller per coat | Maximum 1 kg/m² on vertical surfaces | |
| AK/AE primer | 0.1 kg/m² | 40–50 μm dry film |
| EP61 on galvanised steel | 0.15 kg/m² | 50 μm dry film |
| TOP C / TOP D finish | 0.13 kg/m² | 60 μm dry film |
| Curing | Approx. 24 h per coat | 20°C, 65% RH |
| Drying before finish | At least 48 h and completely dry | Before TOP finish |
| Packaging | 6, 25 or 35 kg plastic pails | White |
| Storage | 5–30°C, sealed and frost-free | 12 months |
| Finish colour | RAL, NCS or agreed sample | For the compatible topcoat |
Application & system
Steel and primer preparation
Remove rust, dust, grease, adhesive, lime residue, moisture and incompatible coatings. Blast-clean to EN ISO12944-4 Sa2.5 or manually prepare to St3. Apply AK or AE primer. Clean and degrease galvanised steel before EP61. Check existing primers and repair transport or corrosion damage with AK.
Application and finish
Stir slowly to a uniform consistency; apply by brush, roller or airless spray. Consumption depends on section factor U/A and dry-film thickness. Maximum brush/roller application on vertical surfaces is 1 kg/m² per coat. Use compatible TOP C / TOP D finishes for moisture protection and cleaning. Topcoat colours may follow RAL, NCS or an agreed sample.
Drying & curing
Curing and topcoating
Each coat cures in approximately 24 hours at 20°C and 65% RH. Allow at least 48 hours and complete drying before TOP finishes. Matrix figures are hours. Low temperature, high humidity and thicker films extend drying.
Drying-time matrix
| RH | Wet film | 10°C still | 10°C airflow | 20°C still | 20°C airflow | 30°C still | 30°C airflow |
|---|---|---|---|---|---|---|---|
| 30% | 0.3 | 6 | 2.5 | 4 | 2 | 4 | 1.5 |
| 30% | 0.6 | 8 | 3.5 | 6 | 3 | 5 | 2.5 |
| 30% | 1.2 | 12 | 4.5 | 8 | 4 | 6 | 3 |
| 50% | 0.3 | 10 | 3 | 6 | 3 | 5 | 1.5 |
| 50% | 0.6 | 12 | 4 | 8 | 4 | 6 | 3 |
| 50% | 1.2 | 18 | 6 | 12 | 5 | 10 | 3.5 |
| 70% | 0.3 | 12 | 6 | 10 | 5 | 8 | 3 |
| 70% | 0.6 | 18 | 9 | 12 | 7 | 10 | 6 |
| 70% | 1.2 | 24 | 12 | 18 | 9 | 12 | 7 |
Conditions & precautions
Weather and storage
Use trained personnel. Material, surface and ambient temperature must be ≥10°C, RH ≤80% and temperature ≥3°C above dew point. PMA is water-sensitive. Protect during application, drying and transport. For unavoidable outdoor work, avoid rain and confirm a suitable sealing system; Chnitherm 800 is a separate exterior-work option. Temporary rain resistance is not permanent exterior suitability. Store sealed at 5–30°C without frost for 12 months. Follow the SDS and prevent discharge to water or soil.
Documents & specification support
Specify for your project.
Share the application, substrate, area and performance requirements to discuss a coordinated system.